DuraVent 2PPS-E45 Installation Guide

Browse online or download Installation Guide for Unknown DuraVent 2PPS-E45. DuraVent 2PPS-E45 Installation Guide User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
PolyPro
®
Installation Instructions
PolyPro Single-Wall Gas Vent
System for Category II & IV
Gas-Burning Appliances
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - Installation Instructions

PolyPro®Installation InstructionsPolyPro Single-Wall Gas Vent System for Category II & IV Gas-Burning Appliances

Page 2 - THESE INSTRUCTIONS

10Lochinvar 2" installation (Fig.14)1. Slide PolyPro pipe w/ PVC adapter into oblong hole and down. Brackets will point away from the wall, on

Page 3 - CONTENTS

11pipe is to be installed on the exhaust outlet.3. Once securely installed to exterior, verify exhaust pipe cannot be removed from termination cap.St

Page 4 - Clearance to Combustibles

128. Install gaskets into Co-Linear Adapter (if applicable). (Fig.13)9. Connect Co-Linear Adapter to termination (if applicable). (Fig.19)10. Insta

Page 5

13M&G DURAVENT POLYPRO CHIMNEY CAP TERMINATIONCOMBUSTION AIR INTAKE FLEX HANGER BRACKET AND HARDWAREAIR INTAKE FLEXFLEX CLAMPM&G DURAVENT POL

Page 6

THIS PAGE INTENTIONALLY LEFT BLANK

Page 7

THIS PAGE INTENTIONALLY LEFT BLANK

Page 8 - ENCLOSURE

PolyPro® is a registered trademark of M&G DuraVent, Inc.All rights reserved, ©2014 M&G DuraVent is a member of M&G Group. Customer Servic

Page 9

A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE

Page 10

3PolyPro Single-Wall Gas Vent SystemFor the most up-to-date installation instructions, see www.duravent.comPolyPro®CONTENTSLISTING. . . . . . . . . .

Page 11

4LISTINGListed to ULC S636 Rated Class IIA, IIB, and IIC vent systemmaximum temperature 230°F (110 °C)maximum positive pressure 15 in-w.c. Massachuset

Page 12

5IMPORTANTTo prevent possible recirculation of ue gases, the installer must consider the eects of prevailing wind conditions, eddy zones, nearby bu

Page 13

Figure 2PUSH DOWN TO LOCKPRY OUT TO UNLOCKVERIFY GASKET IS SEATED IN FEMALE END OF PIPEMALE ENDFEMALE ENDFigure 3APPLIANCE CONNECTION: 2" - 4&

Page 14

INSTALLATION1. Pipe lengths may be cut to length (Fig.6). Use an alternate clamp (Fig.4- PPS-PAC / PPS-LBC) for the connection if a locking button (

Page 15

8Multi-Story: Consult local building or other applicable codes for requirements in your area. In the U.S., NFPA 211 10.6.3 (2013) states: “Vents th

Page 16 - POLYPRO WARRANTY

97. Add additional components to raise vent level if desired (vent to be 12" above grade or average snow level).8. Remove gasket and install Bi

Comments to this Manuals

No comments